I have messed around with NUT to trigger a graceful shutdown of my home server running Ubuntu Server. I have struggled with setting NUT up on bare metal, but would like a gui anyway. I saw PVE-UPS which looks good, but I think but I think it is meant for Proxmox. Any alternatives, or a spin of PVE-UPS for docker compose anybody know about?

  • tychosmoose@lemmy.world
    link
    fedilink
    English
    arrow-up
    1
    ·
    18 hours ago

    A basic NUT configuration does an immediate shutdown as soon as an ONBATT status is reached (upssched.conf has “at ONBATT execute…”, which causes the upssched-cmd to run the shutdown command immediately). But you can change that to a timer, which can be cancelled if the UPS goes back online, or only shutdown at LOWBATT.

    It’s complicated, but NUT should be able to do everything you have stated as a goal. But it takes some testing.

    One thing I found helpful while setting it up is the Dummy UPS driver that is included in the documentation. Rather than plug and unplug a physical UPS during testing you can make text files with various ups statuses and cp one to the dummy’s input file target to make it change to battery power or back online. Use logger to log information into the system journal from upssched-cmd to see what’s running in your script (with a unique keyword to grep on). Monitor in another terminal with journalctl -f | grep yourkeyword to view your messages. This made it much easier to get the upssched stuff sorted out.

    One of my goals was unattended power-on management for when I was away from home. If power returned for an amount of time, send power commands to various smart outlets to bring everything back up in sequence. So I used a pretty big upssched-cmd, with timers for both shutdown and power up and different UPS battery levels (no power up until 30% battery, for example). It would have been pretty difficult to debug without the dummy UPS.

    Anyway, NUT is really powerful.

    • stoicmaverick@lemmy.worldOP
      link
      fedilink
      English
      arrow-up
      1
      arrow-down
      1
      ·
      18 hours ago

      Thanks. Good info. Feel like sharing your conf file to see how it’s formatted in an example that actually works? Might make this my weeks evening project.

      • tychosmoose@lemmy.world
        link
        fedilink
        English
        arrow-up
        4
        ·
        17 hours ago

        It’s a lot. But here are my most recent notes.

        Note that the pipe & lock locations different by distro, as does the nut username. So these files won’t drop in and work anywhere.

        The dummy driver will need to be installed and configured.

        Mine also have several layers of timers on battery an online:

        1. NUT server: In ONBATT I use sleep commands to time subsequent commands. These will always run.
        2. NUT server: Onbatt5 is a upssched timer I set to 300s and is cancelled if the UPS returns to line power.
        3. NUT client: Onbatt30s starts on the client when it gets an ONBATT status from the server.

        Most configs would have the client side cancel their timers if power returns. In my case I don’t want that because I prefer more certainty of state so that I know it’s safe to power cycle an outlet to bring a device back up. My NUT server runs on an old pi 3b with a read-only file system. So it never needs a safe shutdown. It’s the last man standing to bring everything else back up if the UPS returns to line power before the battery is exhausted. That’s why there is no local shutdown on the NUT server config.

        Each snmpset... is a truncated version of an outlet power command.

        Also, the wall commands were a debug aid. Uncomment to use, but test a command first. Wall doesn’t work on some distros.

        NUT Server

        NUT.CONF:

        	MODE=netserver
        

        UPS.CONF:

        	[ups]
        	desc = My UPS
        	driver = dummy-ups
        	port = /opt/ups/ups.seq
        

        UPSD.CONF:

        	LISTEN 0.0.0.0 3493
        	## all interfaces
        	## STATEPATH /var/run/nut
        

        UPSD.USERS:

        	[upsuser]
        	  password = <pw>
        	  actions = set
        	  upsmon master
        	[upssrv]
        	  password = <pw>
        	  actions = set
        	  upsmon slave
        	[upspi]
        	  password = <pw>
        	  actions = set
        	  upsmon slave
        

        UPSMON.CONF:

        	RUN_AS_USER nut
        	#RUN_AS_USER root
        	MONITOR ups@localhost 1 upsuser <pw> master
        	NOTIFYMSG ONLINE "UPS %s on line power"
        	NOTIFYMSG ONBATT "UPS %s on battery"
        	NOTIFYMSG LOWBATT "UPS %s battery is low"
        	NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
        	NOTIFYMSG COMMOK "Communications with UPS %s established"
        	NOTIFYMSG COMMBAD "Communications with UPS %s lost"
        	NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"
        	NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"
        	NOTIFYMSG NOCOMM "UPS %s is unavailable"
        	NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"
        	
        	NOTIFYFLAG ONLINE WALL+EXEC+SYSLOG
        	NOTIFYFLAG ONBATT WALL+EXEC+SYSLOG
        	NOTIFYFLAG LOWBATT SYSLOG+WALL
        	NOTIFYFLAG FSD SYSLOG+WALL
        	NOTIFYFLAG COMMOK SYSLOG+WALL
        	NOTIFYFLAG COMMBAD SYSLOG+WALL
        	NOTIFYFLAG SHUTDOWN SYSLOG+WALL
        	NOTIFYFLAG REPLBATT SYSLOG+WALL
        	NOTIFYFLAG NOCOMM SYSLOG+WALL
        	NOTIFYFLAG NOPARENT SYSLOG+WALL
        	
        	MINSUPPLIES 1
        	SHUTDOWNCMD "/sbin/shutdown -P +0"
        	NOTIFYCMD "/usr/sbin/upssched"
        	POLLFREQ 5
        	POLLFREQALERT 5
        	HOSTSYNC 15
        	DEADTIME 15
        	# POWERDOWNFLAG /var/run/killpower
        	RBWARNTIME 43200
        	NOCOMMWARNTIME 300
        	FINALDELAY 5
        	CERTVERIFY 0
        	FORCESSL 0
        	
        	UPSSCHED.CONF:
        	CMDSCRIPT /etc/nut/upssched-cmd
        	PIPEFN /var/run/nut/upssched.pipe
        	LOCKFN /var/run/nut/upssched.lock
        	
        	AT ONBATT ups@localhost CANCEL-TIMER online3
        	AT ONBATT ups@localhost CANCEL-TIMER online10
        	AT ONBATT ups@localhost START-TIMER onbatt5 300
        	AT ONBATT ups@localhost EXECUTE onbattnotify
        	
        	AT ONLINE ups@localhost CANCEL-TIMER onbatt5
        	AT ONLINE ups@localhost START-TIMER online3 180
        	AT ONLINE ups@localhost START-TIMER online10 600
        	AT ONLINE ups@localhost EXECUTE onlinenotify
        

        UPSSCHED-CMD

        	#! /bin/bash
        	#
        	# This script should be called by upssched via the CMDSCRIPT directive
        	# The first argument passed to your CMDSCRIPT is the name of the timer
        	# from your AT lines.
        	logger -t upssched-cmd "Calling upssched-cmd $1"
        	wall "Calling upssched-cmd $1"
        	UPS="ups@localhost"
        	HOST=$( uname -n)
        	TIMESTAMP=$(date +%Y%m%d%H%M%S)
        	STATUS=$( upsc $UPS ups.status )
        	CHARGE=$( upsc $UPS battery.charge )
        	CHMSG="UPS[STATUS]:$CHARGE%"
        	case $1 in
        			onbattnotify)
        					# srv and pi are upsmon clients and will shut down on their own after a 30s delay.
        					# Log the Notification.
        					logger -t upssched-cmd "UPS on Battery Power. Servers will shutdown in 30 seconds. Switch shutdown in 5 minutes. $CHMSG $TIMESTAMP"
        					wall "upssched-cmd onbattnotify: UPS on Battery Power. Servers will shutdown in 30 seconds. Switch shutdown in 5 minutes. $CHMSG"
        	#                wall "upssched-cmd: sleeping to give servers time to poweroff"
        					sleep 120s
        					# Power off PDU outlets to save power.
        					logger -t upssched-cmd "UPS on Battery Power. PDU outlets 4-srv-drives, 5-srv, 7-pi and 8-homeassistant power down NOW. $CHMSG $TIMESTAMP"
        					snmpset ...
        					snmpset ...
        					snmpset ...
        					snmpset ...
        	#                wall "End upssched-cmd $1"
        					;;
        			onbatt5)
        					# Shut down servers
        					logger -t upssched-cmd "UPS on Battery Power. PDU outlets 3-switch and 8-homeassistant power down NOW. $CHMSG $TIMESTAMP"
        					snmpset ...
        					snmpset ...
        	#                wall "End upssched-cmd $1"
        					;;
        			onlinenotify)
        					# Log the notification.
        					logger -t upssched-cmd "UPS back on Line Power. Bringing up network in 3 minutes, servers in 10 minutes. $CHMSG $TIMESTAMP"
        	#                wall "End upssched-cmd $1"
        					;;
        			online3)
        					# Power on PDU outlets for main switch to prep for server startup.
        					logger -t upssched-cmd "UPS back on Line Power. Bringing up PDU outlet 3-switch NOW. $CHMSG $TIMESTAMP"
        					snmpset ...
        	#                wall "End upssched-cmd $1"
        					;;
        			online10)
        					# Power on PDU outlets for servers now.
        					logger -t upssched-cmd "UPS on Line Power. Bringing up PDU outlets 5-srv, 7-pi, 8-homeassistant NOW. $CHMSG $TIMESTAMP"
        					snmpset ...
        					snmpset ...
        					snmpset ...
        	#                wall "End upssched-cmd $1"
        					;;
        			upsgone)
        					logger -t upssched-cmd "UPS communication has been gone awhile on $HOST. $TIMESTAMP"
        					;;
        			)
        					logger -t upssched-cmd "Unrecognized command: $1"
        					;;
        	esac
        

        NUT Client

        NUT.CONF

        MODE=netclient
        

        UPS.CONF

        maxretry = 3
        

        UPSD.CONF

        # empty
        

        UPSD.USERS

        # empty
        

        UPSMON.CONF

        RUN_AS_USER nut  
          
        MONITOR ups@192.168.0.77 1 upspi <pw> slave  
        NOTIFYCMD /usr/sbin/upssched  
        SHUTDOWNCMD "sudo /sbin/shutdown -P +0"  
          
        NOTIFYMSG ONLINE "UPS %s on line power"  
        NOTIFYMSG ONBATT "UPS %s on battery"  
        NOTIFYMSG LOWBATT "UPS %s battery is low"  
        NOTIFYMSG FSD "UPS %s: forced shutdown in progress"  
        NOTIFYMSG COMMOK "Communications with UPS %s established"  
        NOTIFYMSG COMMBAD "Communications with UPS %s lost"  
        NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"  
        NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"  
        NOTIFYMSG NOCOMM "UPS %s is unavailable"  
        NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"  
          
        NOTIFYFLAG ONLINE WALL+EXEC+SYSLOG  
        #+SYSLOG+WALL  
        NOTIFYFLAG ONBATT WALL+EXEC+SYSLOG  
        #+SYSLOG+WALL  
        NOTIFYFLAG LOWBATT SYSLOG+WALL  
        NOTIFYFLAG FSD SYSLOG+WALL  
        NOTIFYFLAG COMMOK SYSLOG+WALL  
        NOTIFYFLAG COMMBAD SYSLOG+WALL  
        NOTIFYFLAG SHUTDOWN SYSLOG+WALL  
        NOTIFYFLAG REPLBATT SYSLOG+WALL  
        NOTIFYFLAG NOCOMM SYSLOG+WALL  
        NOTIFYFLAG NOPARENT SYSLOG+WALL  
        
        MINSUPPLIES 1  
        POLLFREQ 10  
        POLLFREQALERT 5  
        HOSTSYNC 15  
        DEADTIME 15  
        RBWARNTIME 43200  
        NOCOMMWARNTIME 300  
        FINALDELAY 5
        

        UPSSCHED.CONF

        CMDSCRIPT /etc/nut/upssched-cmd  
        PIPEFN /run/nut/upssched.pipe  
        LOCKFN /run/nut/upssched.lock  
          
        AT ONBATT ups@192.168.0.77 EXECUTE onbattnotify  
        AT ONBATT ups@192.168.0.77 START-TIMER onbatt30s 30
        
        # Disabled the online cancel actions in favor of having certainty on the state.
        # Servers will go down on an OB event, but that's fine. When Nutpi sees it back
        # OL it will bring up the servers
        #AT ONLINE ups@192.168.0.77 CANCEL-TIMER onbatt30s  
        #AT ONLINE ups@192.168.0.77 EXECUTE onlinenotify
        

        UPSSCHED-CMD

        #! /bin/sh  
        #  
        # This script should be called by upssched via the CMDSCRIPT directive.  
        #  
        # The first argument passed to your CMDSCRIPT is the name of the timer  
        # from your AT lines.  
          
        logger -i -t upssched-cmd "Calling upssched-cmd $1"  
        UPS="ups@192.168.0.77"  
        HOST=$( uname -n)  
        STATUS=$( upsc $UPS ups.status 2>&1 | grep -v '^Init SSL' )  
        CHARGE=$( upsc $UPS battery.charge 2>&1 | grep -v '^Init SSL' )  
        CHMSG="$UPS[$STATUS]:$CHARGE%"  
          
        case $1 in  
        onbattnotify)  
        # Log the Notification.  
        logger -t upssched-cmd "UPS on Battery Power. Shutting down $HOST in 30 seconds. $CHMSG"  
        wall "upssched-cmd: UPS on Battery Power. Shutting down $HOST in 30 seconds. $CHMSG"  
        ;;  
        onbatt30s)  
        # Shut down servers  
        logger -t upssched-cmd "UPS on Battery Power. $HOST shutting down NOW. $CHMSG"  
        wall "upssched-cmd: UPS on Battery Power. $HOST shutting down NOW. $CHMSG"  
        sudo shutdown -P +0  
        ;;  
        # onlinenotify)  
        # # Log the notification.  
        # logger -t upssched-cmd "UPS back on Line Power. $HOST is already online. $CHMSG"  
        # wall "upssched-cmd: UPS back on Line Power. $HOST is already online. $CHMSG"  
        # ;;  
        upsgone)  
        logger -t upssched-cmd "UPS communication has been gone awhile on $HOST."  
        ;;  
        *)  
        logger -t upssched-cmd "Unrecognized command: $1"  
        ;;  
          
        esac