Microwave has been on the counter for a few weeks, since neutral on this one kept floating.

Microwave is now back in its cubby, and we have a big increase in counter space.

  • Swordgeek@lemmy.caOP
    link
    fedilink
    arrow-up
    6
    arrow-down
    1
    ·
    5 days ago

    This is a sufficient distance from the sink to not need one.

    We have a bunch of others that will have to swapped for GFCI, eventually. Just not today.

    • flynnguy@programming.dev
      link
      fedilink
      English
      arrow-up
      10
      ·
      5 days ago

      You only really need one, the first outlet in series should be GFCI and then there is a “load” side and anything connected to that is also protected. If you aren’t sure, you can get a tester to trigger a GFCI fault and if it is connected to one, it will trip.

      • Hideakikarate@sh.itjust.works
        link
        fedilink
        arrow-up
        4
        ·
        edit-2
        4 days ago

        We found out on accident that we had one of these. Had an outlet that didn’t work, fuse box wasn’t tripped. Eventually, found one of those outlet buttons on a hidden outlet that was tripped. That was an annoyance.

    • Switorik@sh.itjust.works
      link
      fedilink
      arrow-up
      7
      ·
      5 days ago

      You may want to check what year nec your state has adopted. It unfortunately is required now. Also 20A is required unless you have three or more outlets on the circuit (a duplex counts as two).

      • Nollij@sopuli.xyz
        link
        fedilink
        English
        arrow-up
        11
        ·
        5 days ago

        These usually only apply to new construction. Assuming it was built to code initially, you can replace parts to that same standard forever. You can’t just connect a 15 amp wire (usually 14-gauge) to a 20a outlet/breaker - that would be a horrible violation of all codes. But you can replace that existing 15a outlet as needed.

        You don’t have to run a 20a circuit unless you’re running a new line.

        • Switorik@sh.itjust.works
          link
          fedilink
          arrow-up
          2
          ·
          5 days ago

          You are correct, I assumed the microwave was on a 20A circuit. I’ve had inspectors require me to bring one for one repairs up to code. I suppose it’s an AHJ thing to keep in mind.

      • Swordgeek@lemmy.caOP
        link
        fedilink
        arrow-up
        2
        ·
        4 days ago

        Yeah, I know what my province’s code says and I followed it.

        Also, 20A??! Unless there are three OR MORE outlets??! I don’t know where that would be code. I don’t think I want to know.